Reference Information for Test Currents Per UL 486 UL 1659 UL 310
TEST CURRENT PER UL 486 FOR CONNECTORS INTENDED FOR A SINGLE CONDUCTOR, AMPERES
Conductor Size | Assigned maximum | Static-heating | |
---|---|---|---|
AWG or kcmil | mm2 | ampere rating | test current |
28 | 0.08 | – | 3.5 |
26 | 0.13 | 3.5 | |
24 | 0.20 | 7 | |
22 | 0.324 | 9 | |
20 | 0.519 | – | 12 |
18 | 0.823 | 17 | |
16 | 1.31 | – | 18 |
14 | 2.08 | 15 | [20]30 |
12 | 3.31 | 20 | [25]35 |
10 | 5.261 | 30 | [40]50 |
8 | 8.367 | 50 | 70 |
6 | 13.30 | 65 | 95 |
4 | 21.15 | 85 | 125 |
STATIC HEATING & HEAT-CYCLING TEST CURRENTS PER UL 1659 FOR CONDUCTORS
Wire Size | Static Heating Test | Heat-Cycling Test | |
---|---|---|---|
Wire Size AWG |
mm2 | current amperes | current amperes |
18 | 0.82 | 10 | 20 |
16 | 1.3 | 13 | 25 |
14 | 2.1 | 18 | 32 |
12 | 3.3 | 25 | 37 |
10 | 5.3 | 30 | 45 |
TEST CURRENT PER UL 310 FOR CONNECTORS INTENDED FOR INTERNAL WIRING
Wire Size | Temperature | Heat-Cycling | |||
---|---|---|---|---|---|
AWG | mm2 | 0.110, 0.125 inch (2.8mm), (3.2mm) terminals |
All others | 0.110, 0.125 inch terminals (2.8mm), (3.2mm) |
All other |
22 | 0.32 | 2 | 3 | 4 | 6 |
20 | 0.52 | 3 | 4 | 6 | 8 |
8 | 0.82 | 4 | 7 | 8 | 14 |
16 | 1.3 | 5 | 10 | 10 | 20 |
14 | 2.1 | 15 | 30 | ||
12 | 3.3 | 20 | 40 | ||
10 | 5.3 | 24 | 48 |